Product Overview: The power meter features precise measurement of power parameters, monitoring and analysis of power quality parameters, power energy statistics, over-limit alarm, maximum value recording, and event sequence recording. Through the I/O module, it realizes the monitoring of the status of on-site equipment, remote control, and alarm output. The power meter provides standard communication interfaces and can choose dual communication network redundancy. It also offers power pulse output and 4-20mA analog output functions, which can drive analog and logic quantity preset alarms. The large-screen liquid crystal display interface enables users to easily obtain power parameters.
Product Overview: The power meter features precise measurement of power parameters, monitoring and analysis of power quality parameters, power energy statistics, over-limit alarm, maximum value recording, and event sequence recording. Through the I/O module, it realizes the monitoring of the status of on-site equipment, remote control, and alarm output. The power meter provides standard communication interfaces and can choose dual communication network redundancy. It also offers power pulse output and 4-20mA analog output functions, which can drive analog and logic quantity preset alarms. The large-screen liquid crystal display interface enables users to easily obtain power parameters.
Measurement accuracy:
Voltage: 0.2% for 5V to 5000Kv, Current: 0.2% for 5mA to 50000A
Active power: 0.5% for -100000 to 100000kW, Reactive power: 0.5% for -100000 to 100000kvar
Apparent power: 0.5% for 0 to 100000kVA, Power factor: 0.2% for -1.000 to 1.000, Resolution: 0.001
Active energy: 1% for 0 to 999999999kwh, Reactive energy: 1% for 0 to 999999999kvarh
Frequency: 0.2% for 45 to 65Hz, Resolution: 0.01Hz
Rated current: 5A/1A. The current ratio can be set. Overload capacity: 1.2 times the rated current. Continuous operation. Load < 0.2VA. Accuracy: 0.2%
Voltage input:
Rated voltage: 380V/100V. Voltage ratio can be set. Overload capacity: 1.2 times rated voltage. Continuous operation
Load: <0.2VA. Accuracy: 0.2%
Harmonic indicators:
Measurement values: 2nd to 31st harmonics
Communication Network:
RS485 (standard configuration), Modbus-RTU protocol, 2-core shielded twisted pair cable
Baud rate: 2400 - 19200 bps
Working power supply:
AC/DC control power supply, Working range: 85~264Vac, 50/60Hz; 100~300Vdc
Power consumption < 5W
Relay output:
Contact capacity: 250VAC 5A, 30VDC 5A, Pulse width: 0 - 3000s, SOE resolution: 1ms
Analog output:
Output range: 4 - 20mA within excitation, Output load: 500 ohms
Applicable Environment:
Operating Temperature: -25℃ to 70℃, Storage Temperature: -30℃ to 75℃
Atmospheric Pressure: 80kPa to 110kPa, Relative Humidity: 5% to 95% (no condensation)
Safety (electrical insulation property):
Dielectric strength: 2kV, Insulation resistance: ≥100M