Power Meters
Power Meters
  • Details
  • Function
  • Parameter

Product Overview: The power meter features precise measurement of power parameters, monitoring and analysis of power quality parameters, power energy statistics, over-limit alarm, maximum value recording, and event sequence recording. Through the I/O module, it realizes the monitoring of the status of on-site equipment, remote control, and alarm output. The power meter provides standard communication interfaces and can choose dual communication network redundancy. It also offers power pulse output and 4-20mA analog output functions, which can drive analog and logic quantity preset alarms. The large-screen liquid crystal display interface enables users to easily obtain power parameters.








Product Overview: The power meter features precise measurement of power parameters, monitoring and analysis of power quality parameters, power energy statistics, over-limit alarm, maximum value recording, and event sequence recording. Through the I/O module, it realizes the monitoring of the status of on-site equipment, remote control, and alarm output. The power meter provides standard communication interfaces and can choose dual communication network redundancy. It also offers power pulse output and 4-20mA analog output functions, which can drive analog and logic quantity preset alarms. The large-screen liquid crystal display interface enables users to easily obtain power parameters.









Measurement accuracy:

Voltage: 0.2% for 5V to 5000Kv,   Current: 0.2% for 5mA to 50000A

Active power: 0.5% for -100000 to 100000kW,  Reactive power: 0.5% for -100000 to 100000kvar

Apparent power: 0.5% for 0 to 100000kVA,  Power factor: 0.2% for -1.000 to 1.000,  Resolution: 0.001

Active energy: 1% for 0 to 999999999kwh,  Reactive energy: 1% for 0 to 999999999kvarh

Frequency: 0.2% for 45 to 65Hz,  Resolution: 0.01Hz

Rated current: 5A/1A. The current ratio can be set. Overload capacity: 1.2 times the rated current. Continuous operation. Load < 0.2VA. Accuracy: 0.2%

Voltage input:

Rated voltage: 380V/100V.  Voltage ratio can be set. Overload capacity: 1.2 times rated voltage. Continuous operation

Load: <0.2VA. Accuracy: 0.2%

Harmonic indicators:

Measurement values: 2nd to 31st harmonics

Communication Network:

RS485 (standard configuration), Modbus-RTU protocol, 2-core shielded twisted pair cable

Baud rate: 2400 - 19200 bps

Working power supply:

AC/DC control power supply, Working range: 85~264Vac, 50/60Hz; 100~300Vdc

Power consumption < 5W

Relay output:

Contact capacity: 250VAC 5A, 30VDC 5A,  Pulse width: 0 - 3000s,  SOE resolution: 1ms

Analog output:

Output range: 4 - 20mA within excitation, Output load: 500 ohms

Applicable Environment:

Operating Temperature: -25℃ to 70℃,  Storage Temperature: -30℃ to 75℃

Atmospheric Pressure: 80kPa to 110kPa,  Relative Humidity: 5% to 95% (no condensation)

Safety (electrical insulation property):

Dielectric strength: 2kV,  Insulation resistance: ≥100M


Address:Room 706, Huaxin Building, Yangzhuang Road, Shijngshan District, Beijing
Postcode:100043
TEL:13801042802
Email:stgkdq@vip.163.com
Copyright © 2018-2025 北京斯拓高科电气有限公司 All Rights Reserved.